AlvorAdvisory
Advisory/Data Centre Physical Security

Data centre physical security · Australia

Data centre physical security for the PSPF, the ISM, SOCI and your customers' audits.

A data centre in Australia can answer to the PSPF, the ISM, SOCI and its customers' audits at once, and to the HCF if it hosts government data. One layered design, documented once and mapped to each regime, gives every assessor the same record. Each regime still tests it its own way, and the HCF also looks at who owns and controls the facility. We assess the facility, design the boundaries and prepare the evidence.

Book a consultationHow an engagement runs

Current as of October 2026:PSPF Release 2026, ISM September 2026

Site perimeter
BuildingISM layer 1ISM-0810
Data hallISM layer 2ISM-1053
Cage
RackISM layer 3ISM-1530
Plant and pathways
PowerCoolingFuelMeet-me roomRisersSecurity control room
  1. Site perimeter
  2. BuildingISM layer 1ISM-0810
  3. Data hallISM layer 2ISM-1053
  4. Cage
  5. RackISM layer 3ISM-1530

Second route, from the site gate

Plant and pathways

Power · Cooling · Fuel · Meet-me room · Risers · Security control room

  • Route from outside to the rack
  • Detection at each door
  • ISM layer
  • Other boundary

Illustrative plan, not a site design.

Plan view of a data centre site with five nested boundaries: the site perimeter, the building, the data hall, the cage and the rack. An access route runs from outside through one door in each boundary to the rack, with detection at every door. A second, shorter route from the site gate reaches the plant and pathways: power, cooling, fuel, the meet-me room, risers and the security control room. The building, the data hall and the rack are the ISM's three layers (ISM-0810, ISM-1053 and ISM-1530).
  • PSPF s 23.2deter, detect, delay, respond, recover
  • CIRMP s 11(1)(e)test that you can detect, delay, deter, respond to and recover from a breach

Which rules apply

The rules an Australian data centre can answer to.

The PSPF binds Commonwealth entities, and its Requirements 0084 and 0085 apply the ISM to them on a risk-based approach. Both reach a commercial operator through its government customers.

Find the row that describes your facility. A facility can sit in more than one row, so read every row that fits.

How the PSPF, the ISM, the HCF, the SOCI CIRMP rules and customer audit standards reach an Australian data centre, by situation
Your situationPSPFISMHCFSOCI CIRMPISO 27001 / SOC 2 / PCI DSS
Commonwealth entity, own facilityBinds youBinds you–Does not apply–Does not apply–Does not apply
Commonwealth entity using a commercial facilityBinds youBinds youUse a certified provider1–Does not apply–Does not apply
Operator hosting classified information or systems of government significanceThrough your government customerThrough IRAP or contract2Through your government customer3–Does not applyThrough your customers' audits
Operator whose asset is a critical data storage or processing asset (s 12F)Reference modelReference model–Does not applyBinds you4Through your customers' audits
Operator holding an HCF Strategic certificateThrough your government customerThrough IRAP or contractBinds youReplaced by the s 30AQ report5Through your customers' audits
A critical infrastructure entity's own data centre holding business critical dataReference modelReference model–Does not applyBinds you6–Does not apply
Operator with private customers onlyReference modelReference model–Does not apply–Does not apply7Through your customers' audits
  • Commonwealth entity, own facility

    • PSPF · : Binds you
    • ISM · : Binds you

    Does not apply: HCF, SOCI CIRMP, ISO 27001 / SOC 2 / PCI DSS

  • Commonwealth entity using a commercial facility

    • PSPF · : Binds you
    • ISM · : Binds you
    • HCF · : Use a certified provider1

    Does not apply: SOCI CIRMP, ISO 27001 / SOC 2 / PCI DSS

  • Operator hosting classified information or systems of government significance

    • PSPF · : Through your government customer
    • ISM · : Through IRAP or contract2
    • HCF · : Through your government customer3
    • ISO 27001 / SOC 2 / PCI DSS · : Through your customers' audits

    Does not apply: SOCI CIRMP

  • Operator whose asset is a critical data storage or processing asset (s 12F)

    • PSPF · : Reference model
    • ISM · : Reference model
    • SOCI CIRMP · : Binds you4
    • ISO 27001 / SOC 2 / PCI DSS · : Through your customers' audits

    Does not apply: HCF

  • Operator holding an HCF Strategic certificate

    • PSPF · : Through your government customer
    • ISM · : Through IRAP or contract
    • HCF · : Binds you
    • SOCI CIRMP · : Replaced by the s 30AQ report5
    • ISO 27001 / SOC 2 / PCI DSS · : Through your customers' audits
  • A critical infrastructure entity's own data centre holding business critical data

    • PSPF · : Reference model
    • ISM · : Reference model
    • SOCI CIRMP · : Binds you6

    Does not apply: HCF, ISO 27001 / SOC 2 / PCI DSS

  • Operator with private customers only

    • PSPF · : Reference model
    • ISM · : Reference model
    • ISO 27001 / SOC 2 / PCI DSS · : Through your customers' audits

    Does not apply: HCF, SOCI CIRMP7

  • Binds you
  • Reaches you through someone else
  • Reference model
  • –Does not apply

Reference model: it does not bind you, but it gives you a public, documented model to design and test against.

  1. 1

    PSPF Release 2026 Req 0111 has security classified information and systems of government significance hosted on a cloud or data centre service certified under the HCF or HCF 2. Req 0112 has non-corporate Commonwealth entities buy data centre space through the Data Centre Facilities Supplies Panel.

  2. 2

    PSPF Req 0109 expects cloud providers to hold an IRAP assessment against the latest ISM from the previous 24 months. The ISM is not legally binding unless legislation or a direction requires it. The ISM · IRAP

  3. 3

    Home Affairs paused HCF registration for new providers on 3 November 2025. The PSPF says providers will be able to certify under HCF 2 from late 2026 or early 2027. The Hosting Certification Framework explained

  4. 4

    The enhanced CIRMP rules (LIN 26/075, in force from 10 June 2026) list nine classes in s 4A(1), and critical data storage or processing assets are not one of them. An asset declared under s 51 after 10 June 2026 could still be brought in. The SOCI Act explained · SOCI readiness advisory

  5. 5

    Under SOCI s 30AB(4), the CIRMP Part does not apply to an asset used to provide services covered by an HCF Strategic certificate the responsible entity holds; s 30AQ asks instead for an annual report within 90 days of the end of the financial year, approved by the board where there is one. The carve-out is for Strategic certificates only.

  6. 6

    The CIRMP Rules take a critical infrastructure entity's own data storage system that meets SOCI s 9(7) to be part of that entity's asset, so the asset's own program covers it.

  7. 7

    Private customers can still bring SOCI in. Under s 12F(2), if a customer is the responsible entity for a critical infrastructure asset and you know your asset is used wholly or primarily for a service relating to its business critical data, your asset is a critical data storage or processing asset.

When teams bring us in

Data centre teams usually call us in one of five situations.

Each one starts with a request from a customer, an auditor or a deadline. Here is what we do about each.

  • A government customer asks about Release 2026

    “Our government customer wants to know how we support PSPF Requirements 0111 and 0112.”

    PSPF Release 2026 changed both requirements on 1 July 2026. Req 0111 covers where classified information and systems of government significance are hosted, and Req 0112 covers how non-corporate Commonwealth entities buy data centre space.

    What we do

    We map your facility and its evidence to what each requirement asks of your customer, so their security team gets a straight answer and you know where your evidence stands.

    The HCF explained
  • A customer says your service holds business critical data

    “A customer has told us our service relates to their business critical data.”

    Under SOCI s 12F(3), a responsible entity tells its data storage or processing provider when the service relates to business critical data. Whether that captures your asset turns on whether it is used wholly or primarily for that service.

    What we do

    We work through the test with you and your lawyers against how the facility is actually used. If the asset is captured, we build the physical security part of your CIRMP and the evidence behind it.

    SOCI physical security for data centres
  • Getting ready for HCF 2

    “HCF registration is paused and we want to be ready when HCF 2 opens.”

    Home Affairs paused registration for new providers on 3 November 2025 while it reforms the framework. The PSPF says providers will be able to certify under HCF 2 from late 2026 or early 2027.

    What we do

    We assess physical access security, one of the core capabilities the current HCF ties to ownership and control, and keep the evidence current so the application is not where the work starts.

    The HCF explained
  • A tenant's auditor asks about your access list

    “Our tenant's SOC 2 auditor wants evidence that they review who can enter our facility.”

    SOC 2 CC6.4 restricts physical access to facilities such as data centres, and its points of focus cover creating, modifying, removing and reviewing that access. The tenant owns the review. The access list lives in your systems.

    What we do

    We set up a review your tenants can run and evidence: who holds access to their space, the tenant's sign-off, and every change recorded in your access control system.

  • A zone is due for certification again

    “One of our security zones is due for certification again.”

    PSPF s 24.2.3 makes certification time-limited: recertification follows expiry, a change in business impact level, significant changes to the architecture or controls, or conditions the Accreditation Authority sets. Table 40 also expects electronic access control to run current patches with no obsolete components.

    What we do

    We check the zone against its certified state, find what has drifted, and prepare the evidence for the Certification Authority the PSPF names.

    PSPF security zones explained

Every request lands on the same facility.

We document it once and map the record to each regime that asks.

One layered design

The PSPF and the SOCI rules use the same five verbs, so one layered design answers both.

The PSPF tells you to build all five layers of physical security (s 23.2). CIRMP s 11(1)(e) makes you prove all five by test.

Respond and recover are organisational capabilities, not properties of a fence or a rack.

What CIRMP section 11 requires of a data centre

Built into the facility

Deter
Visible boundaries and controls at the site, the building and the hall.
Detect
Alarms, access logs and monitoring at every door.
Delay
Walls, doors, cages and containers that hold until someone arrives.

Run by your organisation

Respond
Someone who answers the alarm, with an agreed escalation path.
Recover
Restoring service and the controls themselves after a breach.

What we assess

What we assess, and which standard asks for it.

We walk the facility from the site perimeter to the plant room. Each area is checked once and mapped to the clauses that ask for it, so one walk answers every regime.

Data centre physical security assessment areas mapped to the PSPF and ISM, CIRMP section 11, ISO 27001 Annex A.7 and SOC 2
Area and what we checkPSPF / ISMCIRMP s 11ISO 27001 A.7SOC 2
Site and perimeterWhere the site sits, its standoff, site access and parking, and the perimeter line.PSPF Req 0191, Table 36s 11(1)(b)A.7.1CC6.4
Entry, visitors and critical workersWho may enter, how visitors are escorted, and who counts as a critical worker.PSPF Table 38s 11(1)(d)A.7.2CC6.4
Data halls and zonesWhich Security Zone each hall needs, set by the aggregated classification it holds, and the containers that go with it.PSPF Req 0094, Table 22 · ISM-0810, ISM-1053s 11(1)(a)A.7.3, A.7.6CC6.4
Cage, rack and containersCage and rack locks, and the container class the zone and the classification call for.PSPF Table 22 · ISM-1530, ISM-0813s 11(1)(d)A.7.8CC6.4
Keys and credentialsHow keys, cards and codes are issued, changed, removed and reviewed.ISM-1074s 11(1)(d)A.7.2CC6.4
Monitoring and alarmsAlarm class and who certifies it, monitoring coverage, and that no unauthorised person can observe systems or screens.PSPF s 25.6, Table 40 · ISM-0164s 11(1)(c), (1)(e)A.7.4CC6.4
Plant and pathwaysPower, cooling, fuel, the meet-me room, risers and cabling: the plant the HCF treats as core infrastructure.ISM-0813, ISM-1296s 11(1)(a), (1)(b)A.7.11, A.7.12A1.2
Natural hazards and environmentFire, flood, heatwave and the other natural hazards the site faces, and the protections against each.PSPF Table 36s 11(1)(b)A.7.5A1.2
Equipment and media lifecycleEquipment and media secured when not in use, maintenance access, and disposal that leaves nothing recoverable.ISM-0161–No matching clauseA.7.10, A.7.13, A.7.14CC6.5
Response and testingWho answers an alarm, and a test that the arrangements can detect, delay, deter, respond and recover.PSPF s 23.2s 11(1)(c), (1)(e)–No matching clause–No matching clause
Security systems maintenanceAccess control on current patches with no obsolete components, and alarms serviced by an authorised provider.PSPF Table 40, s 25.6–No matching clauseA.7.13–No matching clause
Site and perimeterWhere the site sits, its standoff, site access and parking, and the perimeter line.
PSPF / ISM
PSPF Req 0191, Table 36
CIRMP s 11
s 11(1)(b)
ISO 27001 A.7
A.7.1
SOC 2
CC6.4
Entry, visitors and critical workersWho may enter, how visitors are escorted, and who counts as a critical worker.
PSPF / ISM
PSPF Table 38
CIRMP s 11
s 11(1)(d)
ISO 27001 A.7
A.7.2
SOC 2
CC6.4
Data halls and zonesWhich Security Zone each hall needs, set by the aggregated classification it holds, and the containers that go with it.
PSPF / ISM
PSPF Req 0094, Table 22 · ISM-0810, ISM-1053
CIRMP s 11
s 11(1)(a)
ISO 27001 A.7
A.7.3, A.7.6
SOC 2
CC6.4
Cage, rack and containersCage and rack locks, and the container class the zone and the classification call for.
PSPF / ISM
PSPF Table 22 · ISM-1530, ISM-0813
CIRMP s 11
s 11(1)(d)
ISO 27001 A.7
A.7.8
SOC 2
CC6.4
Keys and credentialsHow keys, cards and codes are issued, changed, removed and reviewed.
PSPF / ISM
ISM-1074
CIRMP s 11
s 11(1)(d)
ISO 27001 A.7
A.7.2
SOC 2
CC6.4
Monitoring and alarmsAlarm class and who certifies it, monitoring coverage, and that no unauthorised person can observe systems or screens.
PSPF / ISM
PSPF s 25.6, Table 40 · ISM-0164
CIRMP s 11
s 11(1)(c), (1)(e)
ISO 27001 A.7
A.7.4
SOC 2
CC6.4
Plant and pathwaysPower, cooling, fuel, the meet-me room, risers and cabling: the plant the HCF treats as core infrastructure.
PSPF / ISM
ISM-0813, ISM-1296
CIRMP s 11
s 11(1)(a), (1)(b)
ISO 27001 A.7
A.7.11, A.7.12
SOC 2
A1.2
Natural hazards and environmentFire, flood, heatwave and the other natural hazards the site faces, and the protections against each.
PSPF / ISM
PSPF Table 36
CIRMP s 11
s 11(1)(b)
ISO 27001 A.7
A.7.5
SOC 2
A1.2
Equipment and media lifecycleEquipment and media secured when not in use, maintenance access, and disposal that leaves nothing recoverable.
PSPF / ISM
ISM-0161
CIRMP s 11
–No matching clause
ISO 27001 A.7
A.7.10, A.7.13, A.7.14
SOC 2
CC6.5
Response and testingWho answers an alarm, and a test that the arrangements can detect, delay, deter, respond and recover.
PSPF / ISM
PSPF s 23.2
CIRMP s 11
s 11(1)(c), (1)(e)
ISO 27001 A.7
–No matching clause
SOC 2
–No matching clause
Security systems maintenanceAccess control on current patches with no obsolete components, and alarms serviced by an authorised provider.
PSPF / ISM
PSPF Table 40, s 25.6
CIRMP s 11
–No matching clause
ISO 27001 A.7
A.7.13
SOC 2
–No matching clause

For every check behind these areas, with the evidence to ask for and the reference in each standard, use our item-level data centre physical security audit checklist.

Standards in scope

Data centre security standards compared: what each one covers

Availability ratings and security standards are often quoted side by side. Here is what each one says it covers on security, in its current edition.

What TIA-942, EN 50600, ISO/IEC 22237, Uptime Tiers, ISO 27001, SOC 2 and PCI DSS cover on security
StandardCurrent editionWhat it covers on security
TIA-942TIA-942-C, May 2024Physical security is one of its subsystems, alongside architecture, telecommunications, power, cooling, fire protection, safety and monitoring. Ratings run from Rated-1 to Rated-4.
EN 50600 and ISO/IEC 22237EN 50600-2-5:2021 · ISO/IEC 22237-6:2024These are the security parts of each series. ISO/IEC 22237-6 covers unauthorised access, intrusion, internal fire, and internal and external environmental events.
Uptime Institute TiersTier CertificationUptime says its topology and operational sustainability standards do not cover security. Tier Certification is an availability and resilience classification, though its evaluation does look at physical security.
ISO/IEC 27001ISO/IEC 27001:2022 (AS/NZS ISO/IEC 27001:2023 in Australia)Annex A holds 14 physical controls, A.7.1 to A.7.14, from perimeters and physical entry to supporting utilities, cabling and secure disposal. ISO 27001 explained
SOC 22017 Trust Services CriteriaCC6.4 restricts physical access to facilities such as data centres to authorised personnel. Its points of focus cover creating, modifying, removing and reviewing access, and points of focus are not mandatory. SOC 2 explained
PCI DSSPCI DSS v4.0.1Requirement 9 covers restricting physical access to cardholder data. PCI DSS explained
TIA-942
TIA-942-C, May 2024
Physical security is one of its subsystems, alongside architecture, telecommunications, power, cooling, fire protection, safety and monitoring. Ratings run from Rated-1 to Rated-4.
EN 50600 and ISO/IEC 22237
EN 50600-2-5:2021 · ISO/IEC 22237-6:2024
These are the security parts of each series. ISO/IEC 22237-6 covers unauthorised access, intrusion, internal fire, and internal and external environmental events.
Uptime Institute Tiers
Tier Certification
Uptime says its topology and operational sustainability standards do not cover security. Tier Certification is an availability and resilience classification, though its evaluation does look at physical security.
ISO/IEC 27001
ISO/IEC 27001:2022 (AS/NZS ISO/IEC 27001:2023 in Australia)
Annex A holds 14 physical controls, A.7.1 to A.7.14, from perimeters and physical entry to supporting utilities, cabling and secure disposal. ISO 27001 explained
SOC 2
2017 Trust Services Criteria
CC6.4 restricts physical access to facilities such as data centres to authorised personnel. Its points of focus cover creating, modifying, removing and reviewing access, and points of focus are not mandatory. SOC 2 explained
PCI DSS
PCI DSS v4.0.1
Requirement 9 covers restricting physical access to cardholder data. PCI DSS explained

How the work runs

We can start at any point in a facility's life, from the facility security plan to recertification.

Data centre work runs on the same four tracks as the rest of the practice. Each stage ends on a decision that stays yours: carry on with us, take it in-house, or stop where you are.

01Assess

A gap assessment against the regimes that apply.

We confirm which regimes reach your facility, walk the five boundaries and the plant, and rank the gaps with the evidence behind each one.

Applicability matrixGap registerEvidence index
Explore Assess
02Architect

Boundaries and zone layout, designed with the entity.

We design the boundaries and zone layout with the Commonwealth entity, as input to its facility security plan under Req 0190. Where construction must follow the ASIO Technical Notes, we design with the SCEC-endorsed consultant or adviser who works from them.

Boundary and zone layoutFacility security plan inputControl map by regime
Explore Architect
03Build

Access control, monitoring and alarm remediation.

We fix access control, monitoring and alarms alongside your facilities team and installers. For Type 1A alarm work, we scope in a SCEC-endorsed Security Zone consultant.

Remediation planInstaller scopesCommissioning evidence
Explore Build
04Operate

Recertification, annual reports and access reviews.

We watch for the changes that trigger recertification, prepare the evidence for the CIRMP annual report or the s 30AQ report, and run the access reviews your tenants' auditors ask for.

Recertification watchAnnual report evidenceAccess reviews
Explore Operate

Certification and accreditation

Who certifies and who accredits.

PSPF Release 2026 keeps the two steps apart: certification confirms the controls, and accreditation accepts the residual risk before operational use (Req 0198).

Who certifies and who accredits data centre security zones, their controls and other regimes in Australia
Facility, control or regimeWho certifiesWho accredits
PSPF Security Zones and their controls
Zones One to FourReq 0196, 0198 · Tables 40, 41The entity's Chief Security Officer, or a delegated security practitionerChief Security Officer or delegate
Zone Five holding TOP SECRET or aggregated information with a catastrophic business impactReq 0197, 0198ASIO-T4Chief Security Officer or delegate
Outsourced facility housing assets with a catastrophic business impactReq 0096ASIO-T4ASD
Sensitive Compartmented Information Facility (SCIF)Req 0199Accredited by ASD under the National SCIF Accreditation Program before operational use
SCEC-approved Type 1A alarm, Zones Four and FiveTable 40A SCEC-endorsed Security Zone consultantCounts towards the zone's accreditation
Commercial alarm (Zones One to Three) and electronic access control (all zones)Table 40A suitably qualified installer or designerCounts towards the zone's accreditation
Other regimes: who signs off
HCF certificationHome Affairs, which administers the HCF. Registration has been paused since 3 November 2025.
IRAP assessmentReq 0109An ASD-endorsed IRAP assessor, against the latest ISM; for cloud providers, within the previous 24 months
SOCI CIRMPNo certifier. Your board, where you have one, approves the annual report
ISO/IEC 27001:2022An accredited certification body
SOC 2A CPA firm, which attests in a SOC 2 report
PCI DSS v4.0.1A Qualified Security Assessor, or a self-assessment
Uptime TierUptime Institute, as an availability and resilience classification
TIA-942Usually a certification body licensed by TIA, rather than TIA itself

PSPF Security Zones and their controls

  • Zones One to FourReq 0196, 0198 · Tables 40, 41
    Who certifies
    The entity's Chief Security Officer, or a delegated security practitioner
    Who accredits
    Chief Security Officer or delegate
  • Zone Five holding TOP SECRET or aggregated information with a catastrophic business impactReq 0197, 0198
    Who certifies
    ASIO-T4
    Who accredits
    Chief Security Officer or delegate
  • Outsourced facility housing assets with a catastrophic business impactReq 0096
    Who certifies
    ASIO-T4
    Who accredits
    ASD
  • Sensitive Compartmented Information Facility (SCIF)Req 0199

    Accredited by ASD under the National SCIF Accreditation Program before operational use

  • SCEC-approved Type 1A alarm, Zones Four and FiveTable 40
    Who certifies
    A SCEC-endorsed Security Zone consultant
    Who accredits
    Counts towards the zone's accreditation
  • Commercial alarm (Zones One to Three) and electronic access control (all zones)Table 40
    Who certifies
    A suitably qualified installer or designer
    Who accredits
    Counts towards the zone's accreditation

Other regimes: who signs off

  • HCF certification

    Home Affairs, which administers the HCF. Registration has been paused since 3 November 2025.

  • IRAP assessmentReq 0109

    An ASD-endorsed IRAP assessor, against the latest ISM; for cloud providers, within the previous 24 months

  • SOCI CIRMP

    No certifier. Your board, where you have one, approves the annual report

  • ISO/IEC 27001:2022

    An accredited certification body

  • SOC 2

    A CPA firm, which attests in a SOC 2 report

  • PCI DSS v4.0.1

    A Qualified Security Assessor, or a self-assessment

  • Uptime Tier

    Uptime Institute, as an availability and resilience classification

  • TIA-942

    Usually a certification body licensed by TIA, rather than TIA itself

Certification stays with the authority each regime names, so the design and the certificate always come from different hands.

For Zone Five areas and SCIFs, we prepare the facility around them and the evidence your cleared staff present.

PSPF security zones explained

Guides

Guides to PSPF zones, the HCF, SOCI physical security and the audit.

Each guide takes one part of this page further, with the clauses quoted and the dates stated.

  • Learn guide

    What are PSPF security zones?

    Zones One to Five in PSPF Release 2026, which zone PROTECTED information needs, and who certifies and accredits each.

    Read the guide
  • Learn guide

    What is the Hosting Certification Framework (HCF)?

    Strategic, Assured and Uncertified, the registration pause since 3 November 2025, and what PSPF Req 0111 and 0112 ask.

    Read the guide
  • Blog

    SOCI physical security for data centres: what CIRMP section 11 requires, and when the enhanced rules apply

    When s 12F captures a data centre, the duties in s 11, and the routes by which the June 2026 enhanced rules can reach one.

    Read the post
  • Blog

    Data centre physical security audit checklist, mapped to the PSPF, ISM, ISO 27001, SOC 2 and SOCI

    Every check, grouped by the five boundaries and the plant, with the evidence to ask for. Printable, with no sign-up.

    Read the post

FAQ

Common questions about data centre physical security

The questions operators and agency security teams bring to a first conversation.

Does the PSPF apply to a commercial data centre?
Not directly. The PSPF binds Commonwealth entities and reaches a commercial operator through them: PSPF Release 2026 Req 0111 has entities host security classified information and systems of government significance on a service certified under the HCF or HCF 2, and Req 0112 has non-corporate Commonwealth entities buy data centre space through the Data Centre Facilities Supplies Panel. Uncertified providers may host UNOFFICIAL and OFFICIAL data.
Does the ISM apply to a private data centre?
Not as law. The ISM is not legally binding unless legislation or a direction requires it, so it reaches a private operator through its customers: through an IRAP assessment against the latest ISM, which PSPF Req 0109 expects cloud providers to have had within the previous 24 months, or through a contract that names it. Its physical guidelines describe three layers: a security zone for the facility, a second zone for the server or communications room, and security containers.
Which zone does PROTECTED information need?
PSPF Release 2026 Table 22 permits PROTECTED technology assets in any of Zones Two to Five, with the container requirement falling as the zone rises: SCEC Class C in Zone Two, SCEC Class C recommended in Zone Three, and a lockable commercial cabinet in Zones Four and Five. Table 23 lets the container requirement drop further when the room is a separate Security Zone inside another. “Zone 4 = PROTECTED” is operator shorthand, not the PSPF's rule.
Who certifies a data centre security zone?
For Zones One to Four, the Commonwealth entity's Chief Security Officer or a delegated security practitioner certifies the zone (Req 0196). ASIO-T4 certifies Zone Five areas holding TOP SECRET or aggregated information with a catastrophic business impact (Req 0197). The Chief Security Officer or delegate then accredits Zones One to Five once the controls are certified and the residual risk is accepted (Req 0198). An outsourced facility housing assets with a catastrophic business impact is certified by ASIO-T4 and accredited by ASD before use (Req 0096).
What does ASIO-T4 certified mean for a data centre?
Under PSPF Release 2026, ASIO-T4 certifies two things: Zone Five areas holding TOP SECRET or aggregated information with a catastrophic business impact (Req 0197), and outsourced facilities that house assets with a catastrophic business impact, which ASD then accredits before use (Req 0096). Zones One to Four are certified by the entity's Chief Security Officer or a delegate.
Do the June 2026 enhanced CIRMP rules apply to data centres?
Not as a class. The enhanced rules (LIN 26/075, in force from 10 June 2026) list nine asset classes in s 4A(1), and critical data storage or processing assets are not one of them. They can still reach a data centre in two ways: an asset declared under s 51 after 10 June 2026, and a critical infrastructure entity's own data storage system that meets s 9(7), which is taken to be part of that entity's asset. The baseline physical security rule, s 11, applies to critical data storage or processing assets either way.
Is an Uptime Tier or TIA-942 rating a security certification?
Neither is a security certification. Uptime Institute says its topology and operational sustainability standards do not cover security, and Tier Certification is an availability and resilience classification, though its evaluation does look at physical security. TIA-942-C (May 2024) covers physical security as one of several subsystems, and its Rated-1 to Rated-4 levels describe protection against physical events. Security assurance comes from PSPF zone certification, ISO/IEC 27001:2022 certification or a SOC 2 report.
When do you need a SCEC-endorsed consultant?
When a Type 1/1A security alarm system is designed, acceptance tested or commissioned. SCEC says the PSPF does not require agencies to engage a SCEC Security Zone Consultant to design and build security zones, but one must be engaged for Type 1/1A alarm work, and PSPF Table 40 has a SCEC-endorsed consultant certify the Type 1A alarm in Zones Four and Five. We scope that consultant in when the work calls for one.
AlvorAdvisory

Talk to us about your facility's next assessment.

Tell us what the facility hosts, who its customers are, and which certificate, report or audit comes next. We scope the work in writing before anyone walks the site.

Book a consultationSee the four tracks
ALVOR

Security architecture management and compliance: connected into one source of truth.

Security,
Simplified.

Platform

  • Overview
  • AI Assistant
  • Secure by Design
  • Asset Management
  • Risk Management
  • Compliance
  • Policy
  • Security Management
  • Third-Party Risk Management
  • Business Continuity

Capabilities

  • Security Architecture
  • Security Design Review
  • Threat Modeling
  • Dependency Mapping
  • Data Governance
  • Components & SBOM
  • System Security Plan
  • Deployment models

Solutions

  • All solutions
  • CISO
  • Security architect
  • GRC lead
  • Engineering leader
  • Startups
  • Mid-Market
  • Enterprise
  • Regulated & Sovereign
  • Australia

Frameworks

  • ISO 27001
  • SOC 2
  • NIST CSF
  • HIPAA
  • GDPR
  • ISM
  • IRAP
  • Essential Eight
  • ASD Essentials
  • SABSA
  • PCI DSS
  • CMMC
  • FedRAMP
  • Control alignment

Advisory

  • Advisory overview
  • Assess
  • Architect
  • Build
  • Operate
  • All engagements

Company

  • About
  • Blog
  • Learn
  • Security
  • Pricing
  • Compare Alvor

© 2026 Alvor Pty Ltd · ABN 40 700 022 546 · All rights reserved.

PrivacyTermsCookie PolicyVulnerability Disclosure